C-Tec CFP Relay Output Card (Reset, Fault, Aux. & Remote Relay Outputs) (CFP762)

Poids:

SKU:

Barcode:

Collections: Fire Alarm Spares, Fuses, Leads, Resistors, EOL

Type de produit: Relay Output Card

Vendeur : SD Fire Alarms

Mots-clés: C-Tec, CFP762, Relay Output Card

Disponibilité:

Description

View larger CFP Relay Output Card (Reset, Fault, Aux. & Remote Relay Outputs)

An optional system expansion device for use withCFP Standard 2-8 Zone Fire PanelsorCFP AlarmSense 2-8 Zone Fire Panels. Provides four panel-controlled volt free relay outputs (reset, fault, aux. fire and remote). PCB mounts inside the CFP fire panel. Reset relay is active during the panel's reset cycle. Fault relay is active in any fault condition. This relay is failsafe and normally energised - if power is removed from the panel the relay will changeover to produce a fault signal. Aux. fire relay is active in an alarm condition provided all relevant delays have expired. Remote relay is active during any Alarm Condition provided all relevant delays have expired. Outputs are NOT designed to switch mains voltages.