2 Zone Gent Fire Alarm Control Panel 75585-02NMB

Weight:

SKU:

Barcode:

Product type: Other

Vendor: Honeywell

Availability:

Description

GENT 2 ZONE FIRE PANEL

The best conventional panel on the market widely used in shops, banks and thousands of commercial premises

The FP585 panel complies fully with the European standardEN54 Parts 2 & 4 and can be used on installations meetingBS 5839: Part 1.

The panel contains its own integral power supply and battery support for two alarm sounder circuits, two auxiliary relay contacts, a zone disablement facility and a one man test and commission facility, all simplifying system design, installation and commissioning.



FEATURES:-
  • Number of Zones - 2
  • Maximum Load Per Zone - 3mA
  • Number of Sounder Circuits - 2
  • Maximum Sounder Circuit Load - 0.5A per circuit (Total Load Not To Exceed 1A)
  • Batteries (Not Included) - 2 x 12V 2.8Ah
  • Battery Standby (Using Above Specified Batteries) - 72 Hours plus 0.5 Hours Alarm Load
  • Aux Relay Contacts - 1 N/O and 1 N/C Pair, 1A at 24V
  • Approx. Weight (With Batteries) - 6.2Kg
  • Relevant Standard - EN54 Parts 2 and 4
  • Approvals - LPCB Approved to EN54 Parts 2 and 4
  • Cable Entry - 13 Top and 13 Rear
  • Cable Type - BS 6387, 2 Core, min 1.5mm Square CSA
  • Class Change Facility - Via Normally Open Push Button Switch Located No More Than 100m From Panel
  • Temperature - Indoor 0 - 40 Degrees Celsius