Description
GENT 2 ZONE FIRE PANEL
Please visit our online shop sdfirealarms for more details
The best conventional panel on the market widely used in shops, banks and thousands of commercial premises
The FP585 panel complies fully with the European standardEN54 Parts 2 & 4 and can be used on installations meetingBS 5839: Part 1.
The panel contains its own integral power supply and battery support for two alarm sounder circuits, two auxiliary relay contacts, a zone disablement facility and a one man test and commission facility, all simplifying system design, installation and commissioning.
FEATURES:-
- Number of Zones - 2
- Maximum Load Per Zone - 3mA
- Number of Sounder Circuits - 2
- Maximum Sounder Circuit Load - 0.5A per circuit (Total Load Not To Exceed 1A)
- Batteries (Not Included) - 2 x 12V 2.8Ah
- Battery Standby (Using Above Specified Batteries) - 72 Hours plus 0.5 Hours Alarm Load
- Aux Relay Contacts - 1 N/O and 1 N/C Pair, 1A at 24V
- Approx. Weight (With Batteries) - 6.2Kg
- Relevant Standard - EN54 Parts 2 and 4
- Approvals - LPCB Approved to EN54 Parts 2 and 4
- Cable Entry - 13 Top and 13 Rear
- Cable Type - BS 6387, 2 Core, min 1.5mm Square CSA
- Class Change Facility - Via Normally Open Push Button Switch Located No More Than 100m From Panel
- Temperature - Indoor 0 - 40 Degrees Celsius
Please visit our online shop sdfirealarms for more details
Any questions please ask